The SMP Substation Gateway is a substation-grade
gateway designed to integrate both existing and new RTUs, IEDs, PLCs and
control centers into a single homogeneous automation system.
The SMP 4-20/8-40 gateway provides the following functions:
- Protocol Translator - Convert standard or proprietary device protocols to
control center protocols such as DNP3, TEJAS, IEC 60870-5-101/103/104 or IEC
61850 (UCA 2.0): one-to-one, one-to-many or many-to-many.
- Data Concentrator - Collect data from all substation devices, regardless
of protocol, and make it available to control centers and the local HMI,
using LAN, WAN or serial connections.
- Terminal Server / Serial Port Switch - Use the SMP to connect to any
substation device for remote maintenance, monitoring and control.
- Automation Processor - Perform local data processing using the built-in automation functions or the IEC-61131 compatible Soft PLC.
The SMP 4-20/8-40 gateway comes with a complete set of Microsoft Windows® based
maintenance and configuration tools. These tools are easy to use and offer
both local and remote access to the SMP configuration, security settings,
log files, communication traces, and system statistics.
With its advanced functions, the SMP 4-20/8-40 provides a cost effective first step
in any substation automation project:
- Upgrade legacy RTUs - Preserve your investment. Use the SMP to connect
your existing RTUs to new control centers, using modern control center
protocols.
- Add new IEDs - Use the SMP to integrate new digital devices such as
protection relays, PLCs or IEDs. Make device data available to both new
control centers and existing legacy control centers.
- Connect to the WAN - Use the SMP to integrate both legacy and modern
serial devices into the corporate WAN.
- Perform remote device maintenance and configuration - Use the SMP to
remotely access any device's maintenance port.
- Access non-operational data - Use the SMP to automatically retrieve
fault, event and disturbance recordings. Provide a single point of access
for non-operational data.
Cybectec's SMP is the field-proven solution to building a modern
automation system, in a Step-by-Step manner, with minimal risk and
substation downtime.
|
|
SMP 4-20 |
SMP 8-40 |
|
Ethernet |
1
10/100BASE-TX
Optional 100BASE-FX |
2
10/100BASE-TX Optional 100BASE-FX |
|
Serial ports |
4
RS-232/422/485
asynchronous or synchronous
1
RS-232 Console |
8
RS-232/422/485
asynchronous or synchronous
1
RS-232 Console |
|
Optional serial ports |
2 x
8
RS-232 or RS-422/485 |
4 x
8
RS-232 or RS-422/485 |
|
Power Consumption |
15
W |
30
W |
Specifications
Physical
1.72" H x 19" W x 11.40" L - 1U
43.6 mm H x 482.6 mm W x 288 mm L
Rugged steel casing
Power Supply
18-36 VDC, 36-75 VDC,
85-264 VAC / 105-370 VDC
Time Synchronization
Modulated or demodulated IRIG-B input
Demodulated IRIG-B distributed to all
connected devices
Automatically sets SMP internal clock
Features
Real-time clock with battery backup
Built-in watchdog timer, power supply
monitoring
Built-in self-diagnostics
Redundancy support for mission-critical
applications
Passthru connections
Built-in web server
Dialup connections
Automation functions: AND/OR logical
functions, input latching, point tagging, and more
IEC-61131 compatible Soft-PLC
Windows®-based configuration and maintenance tools
Connectivity
Maximum device connections: 64
Maximum control connections: 64
Maximum data points: 10,000
Supported Protocols
DNP3, IEC 60870-5-101/103/104, IEC 61850, UCA 2.0, ICCP, MODBUS, SEL, and
most electrical industry proprietary protocols
Environmental
Ambient operating temperature: -25°C to 55°C
Storage temperature: -40°C to 85°C
MTBF
SMP 4-20: 42.2 years
SMP 8-40: 29.7 years
Meets or Exceeds the Following Standards:
IEC 60068-2-1 : Cold
IEC 60068-2-2 : Dry heat
IEC 60068-2-3 : Damp heat, steady state
IEC 60255-22-1 : Fast transient disturbance
IEC 60255-21-1 : Vibration (sinusoidal)
IEC 61000-4-2 : Electrostatic discharge
immunity
IEC 61000-4-3 : Radiated radio-frequency,
electromagnetic field immunity
IEC 61000-4-4 : Electrical fast
transient/burst immunity
IEC 61000-4-6 : Immunity to conducted
disturbances, induced by
radio-frequency fields
IEC 61000-4-11 : Voltage dips, short
interruptions and voltage variations immunity
CE-marking compliant
1 Year Limited Warranty
|